2
VALVES
VAL-352
For further information www.norgren.com
a
P
A
b
a
b
Click-on
®
Solenoid
interchangeable
without
tools
Description (standard valve)
Solenoid valve for hot water and
steam
Switching function: normally closed
Flow direction: determined
Differential pressure: 1.45 psi
(0.1 bar) required
Fluid temperature:
32°F to 302°F (0°C to 150°C)
Ambient temperature:
14°F to 140°F (-10°C to 60°C)
Operating pressure:
1.45 to 145 psi (0.1 to 10 bar)
Mounting position: as required,
preferably with solenoid vertical
on top
Material
Body: Brass
Seat seal: HNBR
Internal parts: Stainless steel, Brass
For contaminated fluids the use of a
strainer upstream of the valve is recom-
mended.
Features
High flow rate
Damped operation
Functional compact design
Solenoid interchangeable without
tools (Click-on®)
Particularly suitable as a water
valve according to DIN EN
60730-2-8
For hot water and steam
Indirectly solenoid actuated
Diaphragm valves
Internal thread 1/4" NPT to 1" NPT
Technical data
Operating pressure psi
Connection size
NPT
Orifice
inch
Cv-Value Weight
(lb)
Part number* HNBR
00
Normally open
01
Manual override
02
1/4 0.3 2.0 1.04 82680XX.9101.XXXXX 1.45 - 145 1.45 - 145 1.45 - 145
3/8 0.4 3.1 0.99 82681XX.9101.XXXXX 1.45 - 145 1.45 - 145 1.45 - 145
1/2 0.5 3.9 1.1 82682XX.9101.XXXXX 1.45 - 145 1.45 - 145 1.45 - 145
3/4 0.8 6.3 1.43 82683XX.9101.XXXXX 1.45 - 145 1.45 - 145 1.45 - 145
1 1.0 9.8 2.09 82684XX.9101.XXXXX 1.45 - 145 1.45 - 145 1.45 - 145
* For orders please state voltage and frequency, e.g.: 8268200.9101.23050 for 230V 50Hz or 8268200.9101.02400 for 24 VDC
DC AC
50Hz 60Hz
24V 24V -
- 110V 120V
- 230V 220V
Solenoid DC AC
Inrush Holding
9101 8W 15 VA 12 VA
Solenoid 9101 (standard voltages) Power consumption
Design according to DIN VDE 0580
Voltage range +/-10%, duty cycle 100%
Protection class according to EN 60529: IP65
Electrical connector according to DIN EN 175301-803 (included)
The solenoids are UL listed and CSA approved
Technical specifications
Series 82680
2/2-way valves Orifice 0.3 to 1.0