Our policy is one of continued research and development. We therefore reserve the right to amend, without notice, the specifications given in this document. (2019 - 9261a) © 2020 IMI International s.r.o. en 1.6.601.044 01/21 Analog Output Module Model Number FX5-4DA-ADP Stocked Item - Certification CE (EMC) Applicable PLCs FX5U/FX5UC Number of Analog Output Points 4 points (4 channels) Digital Input 14-bit binary value Analog Output Voltage -10 to +10 VDC (external load resistance value 1k to 1 MΩ) Analog Output Current 0 to 20 mA DC (external load resistance value 0 to 500 Ω) Output Characteristics, Resolution (*1) Analog Output Range Digital Value Resolution Voltage 0 to 10 V 0 to 16000 625 µV 0 to 5 V 0 to 16000 312.5 µV 1 to 5 V 0 to 16000 250 µV -10 to +10V -8000 to +8000 1250 µV Current 0 to 20 mA 0 to 16000 1.25 µA 4 to 20 mA 0 to 16000 1 µA Accuracy (Accuracy for the Full Scale Analog Output Value) Ambient temperature 25±5°C: ±0.1 % (Voltage ±20 mV, Current ±20 µA) Ambient temperature 0 to 55°C: ±0.2 % (Voltage ±40 mV, Current ±40 µA) Conversion Speed Maximum 950 µs (The data will be updated at every scan time of the PLC.) Isolation Method Between output terminal and PLC: Photocoupler; Between output channels: Non-isolation Number of Occupied I/O Points 0 point (This number is not related to the maximum number of I/O points of the PLC) Weight (kg) 0.1 Dimensions (W x H x D) mm 17.6 x 106 x 89.1